Electric Actuator

Products > Electric actuator > Electric Actuator

Electric Actuator

Product Model: HQ
Motor Power: 110 / 220V AC 1PH, 380 / 440V AC 3PH, 50 / 60Hz, ± 10%
Control Power: 110 / 220V AC 1PH, 50/60 Hz, ± 10%
Motor: Squirrel Cage Asynchronous Motor
Limit Switch: 2 X on / off, SPDT, 250V AC 10A
Stall Protection /Operating Temperature: built-in thermal protection, open 150 ℃ ± 5 ℃ / off 97 ℃ ± 15 ℃
Ambient Temperature: -20 ℃ ~ +70 ℃
Contact purchase
shared:

A Brief Introduction To HQ Electric Actuators

1, Due to the use of high-quality aluminum alloy, light weight. And the inner and outer surfaces are anodized, and the outer surface is coated with polyester powder, and the corrosion resistance is strong. 
2, The motor - using SPG squirrel-cage motor, the output torque is large, and built-in thermal protection switch, the temperature control, to prevent damage to the motor. 

HQ Electric Actuator Features
 1, Shell - due to the use of high-quality aluminum alloy, light weight. And the inner and outer surfaces are anodized, and the outer surface is coated with polyester powder, and the corrosion resistance is strong. 
 2, The motor - using SPG squirrel-cage motor, the output torque is large, and built-in thermal protection switch, the temperature control, to prevent damage to the motor. 
 3, The moving structure - no power, pull the clutch handle can be manually operated. When energized, the clutch is automatically reset. 
 4, The position indicator - the indicator is installed on the central axis, you can observe the valve position. And the indicator light (SLU) to choose from. 
 5, Dryer - used to control the temperature, to prevent the internal condensation of the actuator, to keep the internal electrical components of the dry. 
 6, Limit switch - by the cam mechanism to control, a simple adjustment mechanism can accurately and easily set the locations. 
 7, Torque switch (except HQ-008 outside) - can provide overload protection, to prevent damage to the motor. (Set before the factory is set, please do not change the settings of the user). 
 8, Self-locking - a self-locking function to prevent reversal, rotating part of the stable and reliable. 
 9, The installation - the bottom of the installation size in line with ISO5211 international standards, drive sleeve can be removed according to the need for processing, strong adaptability. Can be installed vertically or horizontally. 
 10, The terminal - the circuit layout is compact and reasonable, the terminal diameter of 2.5mm, pressure, strong connection. 
 11, Worm gear - with concave wheel design, and the contact surface with the worm, transmission torque, smooth and wear, long service life. 
 12, PCU board - compact and reasonable, the PCU board built in the case.


 HQ Electric Actuator Performance Parameters

ModelMaximum
Output
Torque
Action
Time
Maximum 
Shaft Diameter
Motor Class FRated current (A) 60 / 50HzHandwheel 
Turns
Weight
60 / 50HzSimplexThree Phases
Kg-m90 °MMW110V220V380V440VN.Kg
HQ-008813/16Ф20151.10 / 0.950.55 / 0.54N / AN / A107.4
HQ-0151521/25Ф22401.65 / 1.670.88 / 0.840.31 / 0.310.30 / 0.311116.6
HQ-0202021/25Ф22401.67 / 1.670.89 / 0.850.31 / 0.310.30 / 0.311116.6
HQ-0303026/31Ф35401.85 / 1.860.92 / 0.920.35 / 0.350.34 / 0.3413.522
HQ-0505026/31Ф35903.60 / 3.621.55 / 1.580.59 / 0.590.58 / 0.5813.523
HQ-0606026/31Ф35903.65 / 3.621.60 / 2.200.60 / 0.590.59 / 0.5813.523
HQ-0808031/37Ф451804.10 / 4.102.15 / 2.200.85 / 0.850.79 / 0.7916.529
HQ-12012031/37Ф451804.20 / 4.102.35 / 2.300.87 / 0.870.81 / 0.8116.529
HQ-20020093/112Ф651804.10 / 4.102.15 / 2.300.85 / 0.850.79 / 0.7949.575
HQ-30030093/112Ф651804.20 / 4.102.35 / 2.300.87 / 0.870.81 / 0.8149.575

HQ Electric Actuator Standard Parts Technical Parameters
SshellWaterproof Class IP67, NEMA4 and 6
Motor Power Supply110 / 220V AC 1PH, 380 / 440V AC 3PH, 50/60 Hz, ± 10%
Control Power Supply110 / 220V AC 1PH, 50/60 Hz, ± 10%
Load rate (switch)S2 30%
MotorSquirrel Cage Induction Motor
Limit Switch2 X ON / OFF, SPDT, 250V AC 10A
Auxiliary Limit Switch2 X ON / OFF, SPDT, 250V AC 10A (except HQ-008)
Torque SwitchOn / Off, SPDT, 250V AC 10A (except HQ-008)
Stroke90 ° ± 10 ° (0 ° ~ 110 °)
Stall Protection / Operating TemperatureBuilt-in Thermal Protection, Open 150 ℃ ± 5 ℃ / off 97 ℃ ± 15 ℃
IndicatorContinuous Position Indication
Manual OperationMechanical Clutch Mechanism
Self-locking DeviceWorm Gear, Worm Mechanism to Provide Self-locking
Mechanical Limit2 External Adjustment Bolts
Dryer7-10W (110 / 220V AC) Anti-condensation
Wiring Holes2 PF 3/4 "
Ambient Temperature-20 ° C to + 70 ° C
lubricatingAluminum Grease (EP type)
MaterialSteel, Aluminum Alloy, Aluminum Bronze, Polycarbonate
Environment HumidityMaximum 90% RH (non-condensing)
Seismic PerformanceXYZ 10g, 0.2 to 34 Hz, 30 minutes
Outer CoatingDry Powder, Epoxy Polyester

HQ Electric Actuator Optional Technical Parameters
EXAExplosion-proof Housing (Eexd II CT6)HQ Series
WTAWaterproof Housing (IP68, 10M, 250HR)HQ Series
PIUPotentiometer (1K-10K)Except HQ-008
IMSReverse Electromagnetic Control and Transmission of Integrated Motor StartersExcept HQ-008
PCUProportional Control Unit (Input, Output 4-20mADC)Except HQ-008
ATSAdditional Torque Switch (SPDT X2 250V AC 10A)Except HQ-008
LCUField Control Unit (Remote Control / On / Off / Off Selection Switch)Except HQ-008
CPTCurrent Position Sensor (Output 4-20mADC)Except HQ-008
RBPRechargeable Battery (Power Emergency Control)Except HQ-015,020,030,050
EXT120 °, 180 °, 270 ° AngleExcept HQ-200,300
DCMDC Motor (24VDC)Except HQ-015,020,030
LPAHorizontal Installation With Output ArmExcept HQ-008
SLUSignal Indicating Unit (White - Power Supply, Green - Open, Red - Off, Yellow - Torque Overload)Except HQ-008